Compliance Reference Guide

NFPA 10 & OSHA 29 CFR 1910.157 Inspection Requirements

Every portable fire extinguisher in a commercial workplace is governed by four recurring inspection and testing clocks.

1. Monthly Visual Inspection (Every ~30 Days)

Required under NFPA 10 Section 7.2 and OSHA 29 CFR 1910.157(e)(2). Can be performed by trained in-house staff or facility managers without a contractor license — provided each inspection is documented with month, year, and inspector initials.

Open Free Monthly Checklist PDF ›

2. Annual External Maintenance (Every 12 Months)

Must be performed by a certified fire protection technician per NFPA 10 Section 7.3.2, checking mechanical parts, extinguishing agent, and expelling means with an official service tag.

3. 6-Year Internal Maintenance (Stored-Pressure Dry Chemical & Clean Agent)

Every 6 years from manufacture (or last hydrostatic test), stored-pressure extinguishers requiring a 12-year hydro test must be emptied, internally inspected, fitted with new O-rings/valve stems, and recharged (NFPA 10 7.3.6).

Calculate Your 6-Year & 12-Year Dates ›

4. Hydrostatic Testing (Every 5 or 12 Years)

CO2, pressurized water, wet chemical (Class K), and foam cylinders require hydrostatic pressure testing every 5 years. ABC/BC dry chemical and clean agent cylinders require hydrostatic testing every 12 years (NFPA 10 Table 8.3.1).