Deterministic NFPA 10 (2022) Rule Engine
NFPA 10 Hydrostatic Test & 6-Year Maintenance Calculator
Select your fire extinguisher agent type and cylinder manufacture year to calculate every mandatory 6-year internal teardown and 5-year or 12-year hydrostatic test date over the next 24 years.
NFPA 10 Test Interval Quick Reference Table
| Extinguisher Agent | 6-Year Internal Maintenance | Hydrostatic Test Interval | NFPA 10 Citation |
|---|---|---|---|
| ABC Dry Chemical (Stored-Pressure) | Every 6 years | Every 12 years | NFPA 10 Table 7.3.3.1 (6-yr internal) & Table 8.3.1 (12-yr hydro) |
| BC Dry Chemical (Stored-Pressure) | Every 6 years | Every 12 years | NFPA 10 Table 7.3.3.1 (6-yr internal) & Table 8.3.1 (12-yr hydro) |
| Clean Agent (Halotron / FE-36) | Every 6 years | Every 12 years | NFPA 10 Table 7.3.3.1 (6-yr internal) & Table 8.3.1 (12-yr hydro) |
| Carbon Dioxide (CO2) | Not required | Every 5 years | NFPA 10 Table 8.3.1 (5-yr hydro; no 6-yr teardown) |
| Pressurized Water / Water Mist | Not required | Every 5 years | NFPA 10 Table 8.3.1 (5-yr hydro; annual internal where applicable) |
| Class K Wet Chemical (Kitchen) | Not required | Every 5 years | NFPA 10 Table 8.3.1 (5-yr hydro; no 6-yr teardown) |
| AFFF / FFFP Foam | Not required | Every 5 years | NFPA 10 Table 8.3.1 (5-yr hydro; 3-yr agent recharge per 7.8.1.3) |