Deterministic NFPA 10 (2022) Rule Engine

NFPA 10 Hydrostatic Test & 6-Year Maintenance Calculator

Select your fire extinguisher agent type and cylinder manufacture year to calculate every mandatory 6-year internal teardown and 5-year or 12-year hydrostatic test date over the next 24 years.

NFPA 10 Test Interval Quick Reference Table

Extinguisher Agent6-Year Internal MaintenanceHydrostatic Test IntervalNFPA 10 Citation
ABC Dry Chemical (Stored-Pressure) Every 6 years Every 12 years NFPA 10 Table 7.3.3.1 (6-yr internal) & Table 8.3.1 (12-yr hydro)
BC Dry Chemical (Stored-Pressure) Every 6 years Every 12 years NFPA 10 Table 7.3.3.1 (6-yr internal) & Table 8.3.1 (12-yr hydro)
Clean Agent (Halotron / FE-36) Every 6 years Every 12 years NFPA 10 Table 7.3.3.1 (6-yr internal) & Table 8.3.1 (12-yr hydro)
Carbon Dioxide (CO2) Not required Every 5 years NFPA 10 Table 8.3.1 (5-yr hydro; no 6-yr teardown)
Pressurized Water / Water Mist Not required Every 5 years NFPA 10 Table 8.3.1 (5-yr hydro; annual internal where applicable)
Class K Wet Chemical (Kitchen) Not required Every 5 years NFPA 10 Table 8.3.1 (5-yr hydro; no 6-yr teardown)
AFFF / FFFP Foam Not required Every 5 years NFPA 10 Table 8.3.1 (5-yr hydro; 3-yr agent recharge per 7.8.1.3)